Installing Air-Conditioning: Piping, Testing and Maintenance

To install a split air conditioner, fix the indoor unit high on a wall and the outdoor unit on a firm stand with free air around it, join them with insulated copper refrigerant pipes and a drain that slopes down, then test for leaks with dry nitrogen, evacuate the air and moisture with a vacuum pump, open the valves and commission by checking the air temperature drop. Regular cleaning keeps it efficient.

🎬 Step-by-step story

  1. Place the units: the indoor unit high on the wall, the outdoor unit on a firm stand with free air around it.
  2. Join them with two insulated copper pipes and a drain pipe. The drain must slope down all the way.
  3. Pressure test: fill the pipes with dry nitrogen. If the gauge stays steady there is no leak.
  4. Vacuum: a pump pulls out air and moisture. The gauge goes below zero. Then open the valves.
  5. Commissioning: run the unit. The air blows out about 10 °C cooler and water drips from the drain.
  6. Free play: make a leak, and slide the filter from clean to dirty. See what changes.

Tip: drag the 3D scene to turn it. Use two fingers to zoom.

🤔 Common doubts, cleared

Why must the outdoor unit have free space around it?

It throws out the heat taken from the room. If the hot air cannot leave, it is sucked back in and the AC works harder.

Why is the gas pipe thicker than the liquid pipe?

Gas takes much more space than the same amount of liquid, so it needs a wider pipe to flow without a large pressure drop.

Why test with nitrogen and not just air?

Air carries moisture and oxygen, which harm the system. Dry nitrogen is dry and does not react with oil or metal.

Why is the gauge below zero in the vacuum step?

Gauge zero is normal air pressure. A pump removing the air takes the pressure below it, to about −100 kPa.

Where does the drain water come from?

Warm moist air touches the cold coil, and water vapour turns into drops. This is the same as water on a cold glass.

Why does a dirty filter cool less?

It blocks the airflow, so less air passes the cold coil. Slide the filter dirt and watch the ΔT and cooling change.

Equipment installation and piping work

1. Placing the units

2. Refrigerant piping

3. Drain pipe

Water taken from the air must leave. Slope the drain downward at least 1 cm per metre (1:100) with no dips. Do not join it into a sewer without a trap or air break.

4. Power and control

A separate circuit with the right breaker and thick enough cable, earthing and a switch near the outdoor unit.

Testing, inspecting and maintaining air-conditioning

Leak test

Fill the pipes with dry nitrogen (not air, not oxygen) to the pressure the maker states. Watch the gauge for several minutes or hours. A steady gauge means no leak. A falling gauge means a leak: check joints with soapy water (bubbles show the leak). Remember that the gauge also changes a little with room temperature, because gas pressure rises and falls with temperature.

Vacuum

Air and moisture inside would freeze, form acid and damage the compressor. A vacuum pump pulls the pipes down to a deep vacuum (gauge near −100 kPa, or a few hundred microns). Close the pump and wait 15 to 30 minutes: the vacuum must hold. Then open the outdoor valves to let the refrigerant in.

Commissioning (first run)

Maintenance

Key formulas and definitions

Worked examples

1. A drain pipe is 6 m long and must slope 1:100. How much lower is the outlet end?

Drop = 6 m ÷ 100 = 0.06 m = 6 cm.

2. The nitrogen gauge shows 1000 kPa (treat as absolute) at 27 °C. By night it cools to 12 °C. What does the gauge show if there is no leak?

T₁ = 300 K, T₂ = 285 K. P₂ = 1000 × 285 ÷ 300 = 950 kPa. So a small fall may just be the temperature, not a leak. Re-check at the same temperature.

3. Return air is 27 °C and supply air is 17 °C. Is the unit working normally?

ΔT = 27 − 17 = 10 °C, which is in the normal 8 to 12 °C range. Yes.

4. The indoor unit moves 0.15 m³/s of air with ΔT = 10 °C. Find the cooling in kW.

Q = 0.15 × 1.2 × 1.005 × 10 = 1.81 kW (sensible cooling).

5. A unit has 5 m of pipe free of extra charge and needs 20 g per extra metre. The installed pipe is 12 m. How much extra refrigerant?

Extra length = 12 − 5 = 7 m. Extra charge = 7 × 20 = 140 g.

Common mistakes

Practice quiz

1. The gas used for the leak test is:
2. The drain pipe must:
3. What does the vacuum pump remove?
4. Normal air temperature drop across an indoor unit:
5. A dirty filter causes:

Practice: answer these yourself

Type or choose your answer, then press Check. Use a hint if you are stuck; the full solution appears after you answer.

Frequently asked questions

How long does it take to install a split AC?

A trained team usually needs a few hours for a simple install. The vacuum and leak test should never be hurried.

Can I install an AC myself?

Handling refrigerant, electrical work and high-pressure gas need training and tools, so use a trained technician. Learn the steps to check the work.

How often should an AC be serviced?

Clean the filters every month or two and have the coils and refrigerant checked once or twice a year.